COGENERATION: Windsor Cogeneration Specifications
Turbine Supplier HITACHIContractor SNC-LAVALINTURBINEMaximum power output32 MWAnnual average output25 MWInlet pressure (TT valve)4.2...
February 1, 2002 By Pulp & Paper Canada
Turbine Supplier HITACHI
Contractor SNC-LAVALIN
TURBINE
Maximum power output | 32 MW |
Annual average output | 25 MW |
Inlet pressure (TT valve) | 4.263 MPa(a) |
Inlet temperature | 395 Celsius |
Max flow | 430 t/h |
Extraction (section)
Extraction pressure | 1683 MPa(a) |
Extraction temperature | 288 Celsius |
Steam extraction capability flow | 120 t/h |
Exhaust (Section)
Exhaust pressure (design) | 0.869 MPa(a) |
Exhaust temperature | 226 Celsius |
Steam exhaust-capability flow | 340 t/h |
Normal speed | 3600 RPM |
Drive | direct |
Type | Impulse |
Number of stages | 6 |
Governor | GE MarkVI |
Voltage output (generator) | 13.8 kV |
Step-up transformer | 13.8/120 kV |
Synchronization | Automatic |